Optimizer

Design software Energy Optimizer

Reset
Supply
Extract
m³/h
m³/h
Pa
Pa

Winter

°C
%RH
°C
%RH

Heating

°C

Summer

°C
%RH
°C
%RH

LTR-7 Z eWind E

Supply
Extract
73 %
75 %
903 m³/h
950 m³/h
100 Pa
100 Pa
184 W
176 W
1.36 kW/(m³/s)
1246 m³/h
1267 m³/h
191 Pa
178 Pa
38 %
33 %

Sounds

Lw
LwA
64.8 dB
57.6 dB(A)
53.6 dB(A)
50.6 dB(A)
81.9 dB
74.8 dB(A)
73.9 dB
61.7 dB(A)
74.0 dB
61.5 dB(A)
87.0 dB
81.5 dB(A)

Unit information

Ø 250 mm
1510 mm
720 mm
707 mm
130 kg
Supply: F7, ePM1 60 %, bag
Extract: M5, Coarse 80 %, bag
Right
P04 304 0002
400 V/50 Hz, 3~, 3B16A
Unit: 1/4” (internal thread)
5048 W

DWG

Winter

Heat Exchanger

Standard
-26 °C / 90 %RH
13.5 °C / 41 %RH
82.4 %
EN308

Electric heater E

4000 W internal
18.0 °C / 31 %RH
1.38 kW

Annual

St. Petersburg,
Russia
80.1 %
35 370 kWh
814 kWh

Ecodesign

828 W/(m³/s)
1555 W/(m³/s)
1275 W/(m³/s)

Summer

Heat Exchanger

Standard
26 °C / 50 %RH
23.5 °C / 58 %RH
82.4 %
EN308

Electric heater E

4000 W internal
23.5 °C / 58 %RH